Integrated fault detection and supervisory compensation for hydronic radiator faults in district-heated buildings
2026 (English)In: Results in Engineering (RINENG), ISSN 2590-1230, Vol. 32, article id 113471Article in journal (Refereed) Published
Abstract [en]
Hydronic radiator faults in district-heated buildings can degrade comfort, alter return-water temperatures, and increase unnecessary heat use. Although many fault detection and diagnostics studies identify anomalies, fewer close the loop by translating diagnosis into corrective action. This paper develops an integrated fault detection and compensation framework that couples unsupervised anomaly detection with signature-based diagnosis and supervisory setpoint compensation. One-Class Support Vector Machine, Isolation Forest, and Local Outlier Factor models were trained only on fault-free seasonal simulation data and embedded in the EnergyPlus Python API loop for causal, timestep-by-timestep operation. The framework was evaluated using baseline, faulty, and compensation-enabled scenarios, followed by severity sweeps for three representative hydronic faults: a stuck-closed valve, a zone-level over-delivery setpoint-bias proxy for a stuck-open valve, and a system-level supply-temperature setpoint bias. The results show that the achievable supervisory recovery is fault dependent. For the stuck-open proxy, the framework recovered 68.8% of fault-induced discomfort degree-hours and reduced hydronic energy use by 15% relative to the uncompensated fault. For the supply-setpoint bias, recovery reached 57.2%, although the compensation increased the return-water temperature. For the stuck-closed fault, recovery was limited to 38.6%, demonstrating the hydraulic ceiling of supervisory compensation. The severity sweep identified detection floors, saturation regions, and recovery limits. These findings support a fault-specific strategy in which selected control-type faults may be candidates for supervisory compensation, subject to deployable release logic and safety validation, whereas physically constrained faults are prioritized for maintenance.
Place, publisher, year, edition, pages
Elsevier B.V. , 2026. Vol. 32, article id 113471
Keywords [en]
Building energy simulation, District heating, Fault compensation, Fault detection, Hydronic radiator, Anomaly detection, Hydraulic machinery, Radiators, Recovery, Building energy simulations, Fault detection and diagnostics, Faults detection, Heated buildings, Return water, Setpoints, Time step, Water temperatures
National Category
Other Civil Engineering
Identifiers
URN: urn:nbn:se:mdh:diva-79305DOI: 10.1016/j.rineng.2026.113471ISI: 001908466100002Scopus ID: 2-s2.0-105053723018OAI: oai:DiVA.org:mdh-79305DiVA, id: diva2:2113093
Note
This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
2026-10-272026-10-272026-10-28Bibliographically approved