mdh.sePublikationer
Ändra sökning
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf
Estimating the maximum energy-saving potential based on IT load and IT load shifting
Tianjin University of Commerce, China.
Tianjin University of Commerce, China.
Tianjin University of Commerce, China.
Mälardalens högskola, Akademin för ekonomi, samhälle och teknik, Framtidens energi. Tianjin University of Commerce, China.ORCID-id: 0000-0002-6279-4446
Visa övriga samt affilieringar
2017 (Engelska)Ingår i: Energy, ISSN 0360-5442, E-ISSN 1873-6785, Vol. 138, s. 902-909Artikel i tidskrift (Refereegranskat) Published
Abstract [en]

Cooling system consumes more than 35% of total electricity in most data centers. The provided cooling normally exceeds the actual demand of IT equipment in order to assure the safe operation, resulting in a low energy efficiency. In this paper, a novel method based on demand response was proposed to precisely control the cooling supply, and the energy saving potential was assessed systematically. Compared to the reference case, in which the cooling demand is determined by assuming all of servers are in the running status, when the cooling demand was determined based on the measured dynamic IT load at room level, row level, rack level and server level, it can be reduced by 7.9%, 14.2%, 15.6% and 17.9% respectively for the random selected 48 h. In addition, IT load shifting also has a big potential to save energy, as it can make the cooling system working at a higher energy efficiency, which varies with loads. Two cases were studied: even distribution of IT load and optimized IT load shifting. Compared to the best case that determines the cooling demand according to the IT load at server level, they can further reduce the electricity consumption of cooling systems by 0.9%, and 1.2%. 

Ort, förlag, år, upplaga, sidor
Elsevier Ltd , 2017. Vol. 138, s. 902-909
Nationell ämneskategori
Energiteknik
Identifikatorer
URN: urn:nbn:se:mdh:diva-36190DOI: 10.1016/j.energy.2017.07.092ISI: 000415769300074Scopus ID: 2-s2.0-85026462394OAI: oai:DiVA.org:mdh-36190DiVA, id: diva2:1130656
Tillgänglig från: 2017-08-10 Skapad: 2017-08-10 Senast uppdaterad: 2017-12-07Bibliografiskt granskad

Open Access i DiVA

Fulltext saknas i DiVA

Övriga länkar

Förlagets fulltextScopus

Personposter BETA

Li, Hailong

Sök vidare i DiVA

Av författaren/redaktören
Li, Hailong
Av organisationen
Framtidens energi
I samma tidskrift
Energy
Energiteknik

Sök vidare utanför DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetricpoäng

doi
urn-nbn
Totalt: 39 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf